General-purpose Relay
G2R-@-S (S)
CSM_G2R-_-S_(S)_DS_E_1_7
Slim and Space-saving Power Plug-in Relay
■ Reduces wiring work by 60% when combined with the
P2RF-@-PU Push-In Plus Socket
(according to actual OMRON measurements).
■ Lockable test button models available.
■ Built-in mechanical operation indicator.
■ Provided with nameplate.
■ AC type is equipped with a coil-disconnection self-diagnostic
function (LED type).
■ High switching power (1-pole: 10 A).
LR
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
G2R -
-S
(S)
1
2
3
1. Number of Poles
1:
1 pole
2:
2 poles
4
5
4. Rated Coil Voltage
5. Mechanical operation indicator and Nameplate
(S):
Models with mechanical operation indicator and Nameplate
2. Terminals
S:
Plug-in
3. Classification
Blank: General-purpose
N:
LED indicator
D:
Diode
ND: LED indicator and diode
NI:
LED indicator with test button
NDI: LED indicator and diode with test button
Note: Contact your OMRON representative for Relays with gold-plated contacts.
Ordering Information
When your order, specify the rated voltage.
List of Models
Classification
General-purpose
LED indicator
LED indicator with test button
Coil ratings
AC 24, 48, 110, 120, 230, 240
DC 6, 12, 24, 48
Diode
LED indicator and diode
LED indicator and diode with test button
DC 6, 12, 24, 48
Contact form
SPDT
DPDT
G2R-1-S (S)
G2R-2-S (S)
G2R-1-SN (S)
G2R-2-SN (S)
G2R-1-SNI (S)
G2R-2-SNI (S)
G2R-1-SD (S)
G2R-2-SD (S)
G2R-1-SND (S)
G2R-2-SND (S)
G2R-1-SNDI (S)
G2R-2-SNDI (S)
Note: 1. The standard models are compliant with UL/CSA and VDE standards. Also, an EC compliance declaration has been made for combinations with the P2RF-@-E, P2RF-@-S and P2RF-@-PU. The Relays bear the CE Marking.
2. Refer to Connecting Sockets, below, for applicable Socket models.
3. When ordering, add the rated coil voltage and "(S)" to the model number. Rated coil voltages are given in the coil ratings table.
Example: G2R-1-S 12 VDC (S)
Rated coil voltage
1
G2R-@-S (S)
Accessories (Order Separately)
Connecting Sockets
Track/surface-mounting Socket
Applicable Relay model
Push-In Plus
Terminal Blocks
No. of poles
Back-mounting Socket
Screw terminals *
PCB terminals
Solder terminals
Models
Models
Model
Model
1 pole
G2R-1-S (S)
P2RF-05-PU
P2RFZ-05-E
P2RF-05
P2RF-05-E
2 poles
G2R-2-S (S)
P2RF-08-PU
P2RFZ-08-E
P2RF-08
P2RF-08-E
P2R-05P
P2R-057P
P2R-05A
P2R-08P
P2R-087P
P2R-08A
* The structure of P2RF-@-E models provides finger protection. Round terminals cannot be used. Use forked crimp terminals.
Accessories for Push-In Plus Terminal Block Sockets (P2RF-@-PU)
Short Bars
Pitch
No. of poles
Model *
Colors
2
3
7.75 mm
PYDN-7.75-030@
Red (R)
Blue (S)
Yellow (Y)
4
20
15.5 mm
Minimum order (quantity)
PYDN-7.75-020@
PYDN-7.75-040@
10
PYDN-7.75-200@
8
PYDN-15.5-080@
Note: Use the Short Bars for crossover wiring within one Socket or between Sockets.
* Replace the box (@) in the model number with the code for the covering color.
Labels
Model
Minimum order (sheet)
(quantity per sheet)
XW5Z-P4.0LB1
5
1 sheet (60 pieces)
Accessories for Screw Terminal Sockets (P2RFZ-@-E)
Short Bars
Pitch
No. of poles
6.8 mm
10
15.7 mm
Colors
Model
Minimum order (set)
P2DN-6.8-100S
Blue (S)
10
1
One set (order unit) contains
10 short bars and 20 caps.
P2DN-15.7-100S
Note: 1. Use the Short Bars for crossover wiring within one Socket or between Sockets.
2. Cannot be used on the P2RF-@-E.
Labels
Model
Minimum order (sheet)
(quantity per sheet)
XW5Z-P2.5LB1
5
1 sheet (72 pieces)
Accessories for Short Bars (P2DN)
Cap
Model
Minimum order (bag)
1
(100 pcs./bag)
P2DN-CP100
Mounting Tracks
Applicable Socket
Description
Model
Minimum order
(quantity)
50 cm (l) × 7.3 mm (t): PFP-50N
Mounting track
Track-connecting Socket
1 m (l) × 7.3 mm (t):
PFP-100N
1 m (l) × 16 mm (t):
PFP-100N2
End plate *1
PFP-M
Spacer
PFP-S
Back-connecting Socket Mounting plate *2
P2R-P
---
10
1
*1. When mounting DIN rail, please use End Plate (PFP-M).
*2. Used to mount several P2R-05A and P2R-08A Connecting Sockets side by side.
2
G2R-@-S (S)
Specifications
Coil Ratings
Rated current*
Rated voltage
50 Hz
AC
60 Hz
Armature
OFF
43.5 mA
37.4 mA
253 Ω
0.81
48 V
21.8 mA
18.8 mA
1,040 Ω
3.12
6.17
110 V
9.5 mA
8.2 mA
5,566 Ω
13.33
26.83
120 V
8.6 mA
7.5 mA
7,286 Ω
16.13
32.46
230 V
4.4 mA
3.8 mA
27,172 Ω
72.68
143.90
240 V
4.2 mA
3.7 mA
27,800 Ω
90.58
182.34
Rated current*
Coil
resistance
Must
release
voltage
Max.
voltage
% of rated voltage
Power
consumption
(approx.)
1.55
Coil inductance (H)
(ref. value)
Armature
OFF
Must
operate
voltage
Armature
ON
24 V
Rated voltage
DC
Coil
resistance
Coil inductance (H)
(ref. value)
80% max.
30% max.
Must
operate
voltage
Must
release
voltage
Armature
ON
6V
87.0 mA
69 Ω
0.25
12 V
43.2 mA
278 Ω
0.98
2.35
24 V
21.6 mA
1,113 Ω
3.60
8.25
48 V
11.4 mA
4,220 Ω
15.2
29.82
110%
Max.
voltage
% of rated voltage
0.9 VA at 60 Hz
Power
consumption
(approx.)
0.48
70% max.
15% min.
110%
0.53 W
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20% for the AC rated current
and ±10% for the DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage is the maximum possible value of the voltage that can be applied to the relay coil.
It is not the maximum voltage that can be applied continuously.
Contact Ratings
Number of poles
1 pole
Load
Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4; L/R = 7 ms)
Resistive load
(cosφ = 1)
2 poles
Inductive load
(cosφ = 0.4; L/R = 7 ms)
Rated load
10 A at 250 VAC;
10 A at 30 VDC
7.5 A at 250 VAC;
5 A at 30 VDC
5 A at 250 VAC;
5 A at 30 VDC
2 A at 250 VAC; 3 A at
30 VDC
Rated carry current
10 A
5A
Max. switching voltage
440 VAC, 125 VDC
380 VAC, 125 VDC
Max. switching current
10 A
Max. switching power
2,500 VA,
300 W
Failure rate (reference value) *
100 mA at 5 VDC
5A
1,875 VA,
150 W
1,250 VA,
150 W
500 VA,
90 W
10 mA at 5 VDC
Note: P level: λ60 = 0.1 x 10-6/operation
* This value was measured at a switching frequency of 120 operations per minute.
3
G2R-@-S (S)
Characteristics
Item
1 pole
2 poles
Contact configration
SPDT
Contact structure
Single
Contact resistance
100 mΩ max.
Operate (set) time
15 ms max.
Release (reset) time
AC: 10 ms max.; DC: 5 ms max.
(w/built-in diode: 20 ms max.)
Max. operating
frequency
Mechanical:
Electrical:
Insulation resistance
1,000 MΩ min. (at 500 VDC)
Dielectric strength *
5,000 VAC, 50/60 Hz for 1 min between coil and
5,000 VAC, 50/60 Hz for 1 min between coil and contacts;
contacts;
3,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
1,000 VAC, 50/60 Hz for 1 min between contacts of
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
same polarity
Vibration resistance
Destruction:
Malfunction:
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Shock resistance
Destruction:
Malfunction:
1,000 m/s2
200 m/s2 when energized; 100 m/s2 when not energized
Mechanical:
AC: 15 ms max.; DC: 10 ms max.
(w/built-in diode: 20 ms max.)
18,000 operations/hr
1,800 operations/hr (under rated load)
Electrical:
AC coil: 10,000,000 operations min.;
DC coil: 20,000,000 operations min. (at 18,000 operations/hr)
100,000 operations min. (at 1,800 operations/hr under rated load)
Ambient temperature
Operating:
–40°C to 70°C (with no icing or condensation)
Ambient humidity
Operating:
5% to 85%
Weight
Approx. 20 g
Endurance
Note: Values in the above table are the initial values.
* These values are relay only. Prease refer to the “Products Related to Common Sockets and DIN Tracks Data Sheet” for connecting sockets.
Approved Standards
IEC/VDE (Certificate No. 40015012 EN 61810-1)
UL 508 (File No. E41643)
Model
Contact
Coil ratings
form
Contact ratings
Operations
G2R-1-S (S) SPDT
10 A, 30 VDC (resistive)
100 × 103
10 A, 250 VAC (general use)
G2R-2-S (S) DPDT
25 × 103
5 to 110 VDC TV-3 (NO contact only)
6 to 240 VAC 5 A, 30 VDC (resistive)
100 × 103
5 A, 250 VAC (general use)
TV-3 (NO contact only)
25 × 103
CSA 22.2 No.0, No.14
(File No. LR31928)
Model
Contact
Coil ratings
form
Contact
form
Operations
G2R-1-S (S) SPDT
10 A, 30 VDC (resistive)
100 × 103
10 A, 250 VAC (general use)
G2R-2-S (S) DPDT
25 × 103
5 to 110 VDC TV-3 (NO contact only)
6 to 240 VAC 5 A, 30 VDC (resistive)
100 × 103
5 A, 250 VAC (general use)
TV-3 (NO contact only)
Contact ratings
Operations
1 pole
6, 12, 24, 48 VDC
24, 110, 120, 230,
240 VAC
5 A, 440 VAC (cosφ = 1.0)
10 A, 250 VAC (cosφ = 1.0)
10 A, 30 VDC (0 ms)
100 × 103
2 poles
6, 12, 24, 48 VDC
24, 110, 120, 230,
240 VAC
5 A, 250 VAC (cosφ =1.0)
5 A, 30 VDC (0 ms)
100 × 103
LR
Number
of poles
Contact ratings
Coil ratings
Coil ratings
Contact ratings
Operations
1 pole
5 to 110 VDC
6 to 240 VDC
10 A, 250 VAC (general use)
7.5 A, 250 VAC (PF0.4)
10 A, 30 VDC (resistive)
5A, 30VDC (L/R=7ms)
100 × 103
2 poles
5 to 110 VDC
6 to 240 VDC
5 A, 250 VAC (general use)
2 A, 250 VAC (PF0.4)
5 A, 30 VDC (resistive)
3A, 30VDC (L/R=7ms)
100 × 103
25 × 103
4
G2R-@-S (S)
Engineering Data
Maximum Switching Power
G2R-2-S (S)
G2R-1-S (S)
100
Switching current (A)
AC inductive load
(cosφ = 0.4)
AC resistive
load
10
DC resistive
load
DC inductive load
(L/R = 7 ms)
1
0.1
1
10
100
Switching current (A)
100
AC resistive
load
DC resistive
load
1
0.1
1000
AC inductive load
(cosφ = 0.4)
10
DC inductive load
(L/R = 7 ms)
1
Switching voltage (V)
10
100
1000
Switching voltage (V)
Endurance
G2R-2-S (S)
10,000
5,000
1,000
250-VAC/30-VDC
resistive load
500
100
250-VAC inductive load
(cosφ = 0.4)
30-VDC inductive load (L/R = 7ms)
50
Switching current (A)
Endurance (x103 operations)
Endurance (x103 operations)
G2R-1-S (S)
5,000
1,000
500
30-VDC inductive load (L/R = 7ms)
250-VAC/30-VDC
resistive load
100
250-VAC
50 inductive load
(cosφ = 0.4)
Switching current (A)
Maximum voltage (%)
Ambient Temperature vs Maximum Coil Voltage
DC coil
AC coil
Ambient temperature (°C)
5
G2R-@-S (S)
Dimensions
(Unit: mm)
Note: All units are in millimeters unless otherwise indicated.
SPDT Relays
G2R-1-S (S), G2R-1-SN (S), G2R-1-SNI (S)
G2R-1-SD (S), G2R-1-SND (S), G2R-1-SNDI (S)
Terminal Arrangement/Internal Connections
(Bottom View)
G2R-1-SD (S) (DC)
G2R-1-S (S)
29 max.
1
13 max.
1
2
20
35.5 max.
5
4
3
G2R-1-SN (S), G2R-1-SNI (S) (AC)
4.75
2
5
3
4
4
2
5
3
7.5
0.5
1
5
1
24V
3
4
G2R-1-SN (S), G2R-1-SNI (S) (DC)
1
DC
2
5
G2R-1-SND (S), G2R-1-SNDI (S) (DC)
5.2
5.2
17.5
1
2
5
3
4
DPDT Relays
G2R-2-S (S), G2R-2-SN (S), G2R-2-SNI (S)
G2R-2-SD (S), G2R-2-SND (S), G2R-2-SNDI (S)
Terminal Arrangement/Internal Connections
(Bottom View)
G2R-2-S (S)
1
2
3
4
8
7
6
5
13 max.
2.5
35.5 max.
1
2
3
4
8
7
6
5
G2R-2-SN (S), G2R-2-SNI (S) (DC)
1
2
3
4
1
2
3
4
8
7
6
5
8
7
6
5
7.4
8.9
2.4
G2R-2-SN (S), G2R-2-SNI (S) (AC)
6.2
20
29 max.
0.5
G2R-2-SD (S) (DC)
G2R-2-SND (S), G2R-2-SNDI (S) (DC)
5
5
19.4
1
2
3
4
8
7
6
5
6
G2R-@-S (S)
Track/Surface Mounting Sockets
P2RF-05-PU
57.5
Terminal Arrangement/
Internal Connection Diagram
(Top View)
53.1
A2
30.8
28.1
(4.2)
(1)
Mounting Hole
Dimensions
A1
(5)
25.6
Two M3 screw
holes or
two 3.5-dia. holes
108
90
Release lever
35.3
12
(2)
14
(3)
27.35
11
(4)
(4.2)
3.9
15.5
34.3
43
52.1
P2RF-08-PU
Note: Pull out the hooks to
mount the Socket
with screws.
Note: The numbers in
parentheses are
traditionally used
terminal numbers.
25.6
57.5
Terminal Arrangement/
Internal Connection Diagram
(Top View)
53.1
30.8
28.1
(4.2)
A2
(1)
Mounting Hole
Dimensions
A1
(8)
25.6
Two M3 screw
holes or
two 3.5-dia. holes
90
Release lever
35.3
108
12
27.35
(4.2)
3.9
15.5
25.6
34.3
Application
Pitch
PYDN-7.75-@@ (7.75 mm)
3.90
L
12
For Coil
terminals
1.57
PYDN-15.5-080@ (15.5 mm)
3.90
115.85
2.25
7.75 mm
18.5
2.25
12
For Contact
terminals
(common)
15.5 mm
(7)
14
24
(4)
(5)
11
21
(3)
(6)
Note: The numbers in
parentheses are
traditionally used
terminal numbers.
43
52.1
Accessories for P2RF-@-PU
Short Bars
22
(2)
No. of
poles
L (Length)
2
15.1
3
22.85
4
30.6
20
154.6
8
115.85
Colors
Note: Pull out the hooks to
mount the Socket
with screws.
Model *
Maximum
carry current
PYDN-7.75-020@
PYDN-7.75-030@
Red (R)
Blue (S)
Yellow (Y)
PYDN-7.75-040@
20 A
PYDN-7.75-200@
PYDN-15.5-080@
* Replace the box (@) in the model number with the code for the covering color.
Note: 1. Use the Short Bars for crossover wiring within one Socket or between Sockets.
2. When using short bar to coil terminals of PYF-@@-PU, make sure to use PYDN-31.0080@ (31 mm).
When using short bar to coil terminals of P2RF-@@-PU, make sure to use PYDN-15.5080@ (15.5 mm).
18.5
1.57
7
G2R-@-S (S)
P2RFZ-05-E
Terminal Arrangement/
Internal Connection Diagram
(Top View)
2
48 max.
5-M3X8
Mounting Hole
Dimensions
3.2-dia. hole
4
(42.3)
10.5
2
39.5
3
78.5 max.
39.5±0.1
(35.8)
3.5-dia.
hole
35.5
M3 or
3.5-dia.
hole
17.2
4
5
31 max.
16 max.
1
61 max.
P2RFZ-08-E
8-M3X8
Terminal Arrangement/
Internal Connection Diagram
(Top View)
2
48 max.
2
(42.3)
39.5
6
3
7
2
5
4
Mounting Hole
Dimensions
3.2-dia. hole
10.5
39.5±0.1
78.5 max.
(35.8)
3.5-dia.
hole
35.5
M3 or
3.5-dia.
hole
17.2
4
8
1
31 max.
16 max.
61 max.
Accessories for P2RFZ-@-E
Short Bars
P2DN-6.8-100S (6.8 mm)
Maximum carry current: 20A
15.7±0.1
6.8±0.1
2.9
9
15.4 max.
8.7 max.
152.7 max.
2.5 max.
P2DN-15.7-100S (15.7 mm)
Maximum carry current: 20A
2.9
15.7±0.1
1.6-dia.
9
15.4 max.
8.7 max.
152.7 max.
2.5 max.
Note: Each Short Bar set comes with 20 Caps.
Accessories for P2DN
Cap
P2DN-CP100
5.2 max.
4 max.
6 max.
8
G2R-@-S (S)
P2RF-05-E
7±0.2
Five, M3.5´7
2
48 max.
Terminal Arrangement
(Top View)
4
(12)
39.5
3
35.5
85.5 max.
Mounting Holes
(for Surface Mounting)
3.2-dia.
hole
(11)
2
(14)
39.5±0.1
3.5-dia.
hole
M3 or
3.5-dia.
hole
5
(A1)
(A2)
4
1
11.5
61 max.
16.0 max.
Note: Pin numbers in parentheses apply to DIN standard.
P2RF-08-E
6 +0.2
−0.1
2
Terminal Arrangement
(Top View)
2
1.5
Eight, M3´8
48.0 max.
Mounting Holes
(for Surface Mounting)
3
39.5
(21)
(22)
(24)
6
3
7
5
2
4
(11)
(12)
(14)
3.2-dia.
hole
35.5
39.5±0.1
85.5
max.
3.5-dia. hole
8
(A1)
(A2)
4
61.0
max.
1
M3 or
3.5-dia.
hole
11.5
16.0 max.
P2RF-05
2
7
Terminal Arrangement
(Top View)
Five, M3.5 x 8
4-dia. holes
Mounting Holes
(for Surface Mounting)
4.2-dia. hole
35.5
71.5 max.
30±0.05
4
19.5
30 max.
19.5 max.
M3 or 3.2-dia.
hole
54 max.
P2RF-08
2
7
Eight, M3.5 x 8
4-dia. holes
Terminal Arrangement
(Top View)
Mounting Holes
(for Surface Mounting)
4.2-dia. hole
35.5
71.5 max.
30±0.05
4
19.5 max.
19.5
30 max.
54 max.
M3 or 3.2-dia.
hole
9
G2R-@-S (S)
Mounting Height of Relay with Track/Surface Mounting Sockets
P2RF-05-PU
P2RF-08-PU
G2R-@-S (S)
Relay
G2R-@-S (S)
Relay
P2RF-05ーPU
Socket
P2RF-08ーPU
Socket
63.6
63.6
28.1
28.1
(3.9)
(3.9)
P2RFZ-E
G2R-@-S (S)
Relay
P2RFZ-@-E
Socket
67.0 70.5
P2RF-@
P2RF-@-E
G2R-@-S (S)
Relay
G2R-@-S (S)
Relay
P2RF-@-E
Socket
P2RF-@
Socket
66.5 62.0
67.0 70.5
10
G2R-@-S (S)
Back-connecting Sockets
P2R-05P (1-pole)
4
1
Terminal Arrangement
(Bottom View)
14.5 max.
7
Mounting Holes
Tolerance: ±0.1
4
6
4.5
6
35.5 max.
15
Five,
1.6-dia.
holes
4.5
1.2
4
15
3.5
4
1.5
(5)
4
7
7
36.5 max.
P2R-08P (2-pole)
4
0.3
Terminal Arrangement
(Bottom View)
14.5 max.
7
Mounting Holes
7.5
Eight, 1.3-dia. holes
5
5
5
35.5 max.
20
1
5
20
2.8
1.5
(4.3)
7.5
Terminal plate thickness: 0.3
4.5
P2R-05A (1-pole)
36.5 max.
7.5
1.2
0.3
14.5 max.
Terminal Arrangement
(Bottom View)
6.7
3.8
35.5 max.
5
16.7
Panel Cutout
Five, 3 x 1.8-dia. holes
13.6±0.1
6
36.5 max.
Terminal plate thickness: 0.3
30.5±0.2
6.5 7.5
P2R-08A (2-pole)
0.3
14.5 max.
1.2
5
5
35.5 max.
20
2.6
Recommended thickness of
the panel is 1.6 to 2.0 mm
2.8
1.5
Eight, 3 x 1.2-dia. holes
7.5
Terminal plate thickness: 0.3
36.5 max.
11
G2R-@-S (S)
P2R-057P (1-pole)
0.7
14 max.
8.7
1
Mounting Holes
Terminal Arrangement
(Bottom View)
16.4
10.4 3.5
4±0.1
1
6
4.5
15
37 max.29.6
1
8.7
Five,
1.6-dia.
holes
6±0.1
4
8.75
4.5±0.1 15±0.1
4±0.1
5
7.4
7±0.1
41 max.
P2R-087P (2-pole)
14 max.
7.5
1
Mounting Holes
Terminal Arrangement
(Bottom View)
16.4
10.4 3.5
0.3
7.5
5
5
37 max. 29.1
20
1
5
5
8.1
8.9
Eight,
1.3-dia.
holes
20
7.4
(8.1)
41 max.
Mounting Height of Relay with Back-connecting Sockets
P2R-@P
P2R-@A
P2R-@7P
G2R-@-S (S) Relay
G2R-@-S (S) Relay
44.5
G2R-@-S (S) Relay
47.5
38.0
P2R-@P
Socket
P2R-@A
Socket
P2R-@7P
Socket
Mounting Tracks
PFP-100N, PFP-50N
PFP-100N2
16
7.3±0.15
4.5
4.5
35±0.3
15
25
25
10
1,000 (500)
25
25
10
15 (5)
35±0.3 27
27±0.15
1
15
25
25 15
25
25
10
10
24
29.2
1
1.5
1,000
It is recommended to use a panel 1.6 to 2.0 mm thick.
12
G2R-@-S (S)
End Plate
Spacer
10
6.2
PFP-M
PFP-S
16
12
5
1.8
1
50
1.8
11.5
10
M4 x 8 pan
head screw
35.5 35.3
34.8
44.3
1.3
4.8
16.5
Mounting Plate
P2R-P
90
R2.25
10-Ellipse hole
4.5
13.6
3.4
49 42±0.1
30.5
18±0.15 18±0.15 18±0.15 18±0.15
Square hole
9±0.1
72±0.2
9±0.1
t=1.6 mm
13
G2R-@-S (S)
Safety Precautions
Be sure to read the Common Precautions for All Relay in the website at the following URL:
http://www.ia.omron.com/.
Refer to Products Related to Common Sockets and DIN Tracks for precautions on the applicable Sockets.
Refer to PYF-@@-PU/P2RF-@@-PU for precautions on Push-In Plus Terminal Block Sockets.
Warning Indications
CAUTION
Indicates a potentially hazardous
situation which, if not avoided, may result
in minor or moderate injury or in property
damage.
• When cutting with a tool, insert the tool from the plastic part and cut
along the slot in the plastic part between terminals. If you cut a part
other than the slot in the plastic part between terminals, it may not
be possible to attach the insulating cap.
Supplementary comments on what to do
Precautions for or avoid doing to prevent failure to
operate, malfunction, or undesirable
Correct Use
effects on product performance.
Cation
• Do not use the test button for any purpose other than testing. Be
sure not to touch the test button accidentally as this will turn the
contacts ON. Before using the test button, confirm that circuits, the
load, and any other connected item will operate safely.
• Check that the test button is released before turning ON relay circuits.
• If the test button is pulled out too forcefully, it may bypass the momentary testing position and go straight into the locked position.
• Use an insulated tool when you operate the test button.
• When using a cut short-circuit bar (P2DN), always use the provided cap to protect the charger part.
Precautions for Correct Use
About the Built-in Diodes
The diodes that are built into the Relays are designed to absorb
reverse voltage from the Relay’s coil. If a large surge in voltage is
applied to the diode from an external source, the element will be
destroyed.
If there is the possibility of large voltage surges that could be applied
to the elements from an external source, take any necessary surge
absorption measures.
• The proper orientation for installing the short-circuit bar is with the
molded part facing inward.
Latching Levers
• Turn OFF the power supply when operating the latching lever.
After you use the latching lever always return it to its original state.
• Do not use the latching lever as a switch.
• The latching lever can be used for 100 operations minimum.
Relay Replacement
To replace the Relay, turn OFF the power supply to the load and
Relay coil sides to prevent unintended operation and possible
electrical shock.
Coil tape color
Pink tape is used for the AC coil type and blue tape is used for the DC
coil type, making it easy to distinguish AC and DC.
Using a short-circuit bar
• Use the short-circuit bar that is suitable for the socket you are using
and the location of use.
• Note that the P2DN short-circuit bar for the P2RFZ-E Socket has
both a short-circuit bar for shorting coil terminals and a short-circuit
bar for shorting contact COM terminals.
• The short-circuit bar can be cut to match any number of poles. Cut
with a tool as appropriate for the number of relays and sockets.
When using a cut short-circuit bar, take care to avoid injuring yourself on the cut surface.
• Use the short-circuit bar to short-circuit two or more coil terminals,
or two or more contact COM terminals.
• Do not use a deformed short-circuit bar. Risk of failure, malfunctioning, or deterioration of characteristics.
• In socket terminals, insert the short-circuit bar in the correct orientation all the way into all terminals, and then secure with screws.
• Install the short -circuit bar before wiring.
Equivalent Labels from Other Companies and
Recommended Label Printers
Use the following label printer.
The following table gives the manufacturer’s model number as of
March 2017.
Manufacturer
Label
Label printer
Omron
Phoenix
Contact
XW5Z-P4.0LB1
UCT-TM6
XW5Z-P2.5LB2
UCT-TMF5
--- *
BLUEMARK
CLED,
THERMOMA
RK CARD
SET PLUS,
THERMOMA
RK CARD
Weidmuller
MF 10/6
---
Cembre
MG-CPM-04
41391
---
PrintJet
ADVCANCED,
Plotter MCP Markingenius
Plus,
MG3
Plotter MCP
Basic
* When using a printing tool, use a Phoenix Contact label printer.
Note: Ask the label manufacturer or printer manufacturer for details.
14
OMRON AUTOMATION AMERICAS HEADQUARTERS • Chicago, IL USA • 847.843.7900 • 800.556.6766 • automation.omron.com
OMRON CANADA, INC. • HEAD OFFICE
Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • automation.omron.com
OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE
São Paulo, SP, Brasil • 55 11 5171-8920 • automation.omron.com
OMRON ELECTRONICS DE MEXICO • HEAD OFFICE
Ciudad de México • 52.55.5901.4300 • 01.800.386.6766 • mela@omron.com
OMRON ARGENTINA • SALES OFFICE
Buenos Aires, Argentina • +54.11.4521.8630 • +54.11.4523.8483
mela@omron.com
OMRON ELECTRONICS DE MEXICO • SALES OFFICE
San Pedro Garza García, N.L. • 81.12.53.7392 • 01.800.386.6766 • mela@omron.
com
OTHER OMRON LATIN AMERICA SALES
+54.11.4521.8630 • +54.11.4523.8483 • mela@omron.com
OMRON ELECTRONICS DE MEXICO • SALES OFFICE
Eugenio Garza Sada,León, Gto • 01.800.386.6766 • mela@omron.com
Controllers & I/O
• Machine Automation Controllers (MAC) • Motion Controllers
• Programmable Logic Controllers (PLC) • Temperature Controllers • Remote I/O
Authorized Distributor:
Robotics
• Industrial Robots • Mobile Robots
Operator Interfaces
• Human Machine Interface (HMI)
Motion & Drives
• Machine Automation Controllers (MAC) • Motion Controllers • Servo Systems
• Frequency Inverters
Vision, Measurement & Identification
• Vision Sensors & Systems • Measurement Sensors • Auto Identification
Systems
Sensing
• Photoelectric Sensors • Fiber-Optic Sensors • Proximity Sensors
• Rotary Encoders • Ultrasonic Sensors
Safety
• Safety Light Curtains • Safety Laser Scanners • Programmable Safety Systems
• Safety Mats and Edges • Safety Door Switches • Emergency Stop Devices
• Safety Switches & Operator Controls • Safety Monitoring/Force-guided Relays
Control Components
• Power Supplies • Timers • Counters • Programmable Relays
• Digital Panel Meters • Monitoring Products
Switches & Relays
• Limit Switches • Pushbutton Switches • Electromechanical Relays
• Solid State Relays
Software
• Programming & Configuration • Runtime
J140-E3-02
Note: Specifications are subject to change.
© 2020 Omron. All Rights Reserved.
Printed on recycled paper.
Printed in U.S.A.